Full Generator - Türkiye

Diesel Generators


 
 
 
FN 80

FN 80

  • Engine: YANGDONG
  • Engine Model : YD4EZLD
  • Stand By kVA: 80
  • Stand By kW : 64
  • Prime kVA: 72
  • Prime kW : 57,6
  • Rated Current :
SPECFICATIONS
Engine
- YANGDONG heavy duty diesel engine
- 12V starter and charge alternator
- Replaceable air, fuel and oil filters
- Mechanical governor control
- Tropical type radiator
- Flexible fuel hose
- Oil drain valve and extension hose
- Industrial type silencer and steel compensator
- Maintenance-free starter battery
- Water jacket heater
- 1500 rpm engine speed
Sound Proof Canopy and Chassis
- Convenient design for easy lifting and carrying
- High standard sound proof canopy design
- Modular design with easily removable nuts - bolts
- Lockable doors
- Transparent window for watching Control Panel
- Electrostatic powder painted, providing protection against harsh weather conditions
- Emergency STOP button
- Fuel tank inside the chassis
- Anti-vibration wedges (engine - chassis and chassis – ground)
Alternatör
- IP 21-23 Protection Standard
- H Insulation Class
- 50 Hz Frequency
- 4 pole brushless synchronous type alternator
- Automatic Voltage Regulator (AVR)
- 400/230V AC Output Voltage - 1500 rpm
Optional
- Thermal magnetic CB (for automatic models)
- Super Silent Canopy
- Mobile Generator Sets
- Automatic fuel filling system
- Synchronization panel
- 3 Pole and 4 Pole ATS (Automatic Transfer Switch)
- Fuel Heater, Oil Heater
- External fuel tank and automatic fuel filling system
- Fuel - water separator filter
- Remote monitoring and control system
ENGINE
Engine   YANGDONG
Engine Model   YD4EZLD
Number of Cylinders   4 Inline
Injection System   Direct
Compression Ratio   18
Bore   105
Strok   118
Displacement lt 4.1
Air Intake   Turbo-Charger with intercooler
Speed (RPM)   1500
Oil Capacity lt 11
Standby Power kW / hp 69.3 / 93.5
Prime Power kW / hp 63 / 85
Fuel Type   Euro Diesel
Governor System   Electronic
Cooling System   Water Cooling
Coolant Capacity lt 15.1
Fuel Consumption (lt / h) lt Full Load 12.9
lt %75 LOAD 10.5
lt %50 LOAD 7.8
ALTERNATOR
Frequency Hz 50
Power kVA 80
Voltage V 400 V
Number of Phases   3
Automatic Voltage Regulator (A.V.R.)  
Voltage Regulation   ±1%
Insulation Class   H
Protection Standard   IP23
Power Factor   0.8
DIMENSIONS
Weight (Silent) kg 1100
Weight (Open) kg 920
Width (Silent) mm 1000
Length (Silent) mm 2400
Height (Silent) mm 1500
Fuel Tank Capacity lt 170
1 Standby Power : The max power available during a variable electrical power sequence, under the stated operating conditions, for which a generating set is capable of delivering in the event of a utility power outage. Overloading isn’t permissible.
2 Prime Power : The maximum power which a generating set is capable of delivering continuously whilst supplying a variable electrical load. Average load should be 70%. The generator can be overloaded 10% for 1 hour per 12 hrs.
Topçular A.Ş. reserves the right to make changes in model, technical specifications, color, equipment & accessories without prior notice.