FULL 900 KVA DIESEL GENERATOR PERKINS ENGINE

FULL 900 KVA PERKINS ENGINE DIESEL GENERATOR

Standby (kVA)
900 kVA
Standby (kW)
720 kW
Prime (kVA)
818 kVA
Prime (kW)
655 kW
Continuous Output Current (Ampere)
1178
Frequency
50 Hertz
PDF Get a Quote
Engine
Engine Brand PERKINS
Engine Model 4006-23TAG3A
Number and Type of Cylinders 6 Inline
Injection and System Type Direkt
Compression Ratio 13.6:1
Diameter 160 mm
Stroke 190 mm
Cylinder Displacement 22.9 L
Air Suction Power Turbocharged & Air To Air Charge Cooled
Rotational Speed 1500 Revolutions per Minute
Crankcase Oil Capacity (Lt) 114 L
Standby Power 786 / 1053
Prime (PRP) 705 / 945
Fuel Type Euro Diesel
Governor System Mechanical
Cooling Method Water Cooled
Coolant Capacity 105 L
Fuel Consumption at Full Load 172 L
Fuel Consumption at 75% Load 130 L
Fuel Consumption at 50% Load 90 L
Alternator
Frequency (Alternator) 50 Hertz
Voltage 400 Volt
Phase 3
Voltage Regulation ±1%
Insulation Class H
Protection Class IP23
Power Factor 0.8 Ratio
Dimensions
Weight (With Canopy / Without Canopy) 8200 (6400) kg
Width (With Canopy / Without Canopy) 2300 (2300) mm
Length (With Canopy / Without Canopy) 6000 (6000) mm
Height (With Canopy / Without Canopy) 3385 (3385) mm
Fuel Tank Capacity 1600 L